Hitachi L300P Manuale Utente Pagina 123

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 122
“C” Group: Intelligent Terminal Functions
Configuring Drive
Parameters
3–54
Analog Signal
Calibration
Settings
The functions in the following table configure the signals for the analog output terminals. Note
that these settings do not change the current/voltage or sink/source characteristics – only the
zero and span (scaling) of the signals.
NOTE: Settings C081, C082, C083, C121, C122, C123 are factory-calibrated for each inverter.
Do not change these settings unless absolutely necessary. Note that if you restore factory
defaults for all parameters, these settings will not change.
“C” Function
Run
Mode
Edit
Lo Hi
Defaults
Units
SRW Display
Func.
Code
Name Description
–FE2
(CE)
–FU2
(UL)
–FR
(Jpn)
C081 [O] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated
>C081 O-ADJUST
TOP 02119
C082 [OI] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated
>C082 OI-ADJUST
TOP 02512
C083 [O2] input span calibra-
tion
Range is 0 to 65530 ✔ ✔ Factory-calibrated
>C083 O2-ADJUST
TOP 02818
C085 Thermistor input tuning Range is 0.0 to 1000 ✔ ✔
105.0 105.0 105.0
>C085 THERM
ADJUST 0105.0
C086 [AM] terminal offset
tuning
Range is 0.0 to 10.0V ✔ ✔ 0.0 0.0 0.0 V
>C086 AM-MONITOR
OFFSET 00.0V
C087 [AMI] terminal meter
tuning
Range is 0.0 to 250% ✔ ✔ 80. 80. 80. %
>C087 AMI-MON
ADJUST 080
C088 [AMI] terminal offset
tuning
Range is 0 to 20mA ✔ ✔ Factory-calibrated mA
>C088 AMI-MON
OFFSET 04.0mA
C121 [O] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated
>C121 O-ADJUST
ZERO 00000
C122 [OI] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated
>C122 OI-ADJUST
ZERO 00000
C123 [O2] input zero calibra-
tion
Range is 0 to 6553 (65530) ✔ ✔ Factory-calibrated
>C123 O2-ADJUST
ZERO 03622
Vedere la pagina 122
1 2 ... 118 119 120 121 122 123 124 125 126 127 128 ... 263 264

Commenti su questo manuale

Nessun commento